Activating Reset Of Protection / Errors In Manual Mode - Siemens SITRANS PCS 7 Function Manual

Library
Table of Contents

Advertisement

4.28

Activating reset of protection / errors in manual mode

Feature bit
Number of the Feature bit: 31
Activating reset of protection / errors in manual mode
Use this Feature bit to specify whether a reset is necessary once the "Protection" interlock
signal is present again. Also refer to the "Resetting the block in case of interlocks or errors"
section of the manual of the Standard APL blocks.
The default setting is 0.
Bit = 0: No resetting necessary in manual mode.
Bit = 1: Resetting is necessary in manual mode. The reset is performed using the "Reset" button
(RstOp = 1) or, in CFC, using the input parameter RstLi.
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
Configurable response using the Feature I/O
4.28 Activating reset of protection / errors in manual mode
63