Sipps2Pa Connections - Siemens SITRANS PCS 7 Function Manual

Library
Table of Contents

Advertisement

Associated value
7
8
9
10
The associated values 4 to 8 are assigned to the parameters ExtVa304 ... ExtVa308 and can
be used by yourself. Additional information is available in the "Process Control System PCS 7
- Engineering System" manual.
8.1.6

SipPS2PA connections

Input parameters
Parameter
FW
A1*
A1Act
A2*
A2Act
A_AH_MsgEn
A_AL_MsgEn
A_WH_MsgEn
A_WL_MsgEn
AcyclData
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
Block parameters
ExtVa307
ExtVa308
Reserved
Reserved
Description
Firmware version of the device
Response threshold, alarm 1 (Si‐
part alarm module)
1 = Alarm 1 of alarm module ac‐
tive
Response threshold, alarm 2 (Si‐
part alarm module)
1 = Alarm 2 of alarm module ac‐
tive
1 = Enable A1/A2 alarm limit
(high)
1 = Enable A1/A2 alarm limit (low) BOOL
1 = Enable A1/A2 warning limit
(high)
1 = Enable A1/A2 warning limit
(low)
Acyclic data from driver block
PiDr256 (interconnect this input
with AcyclData output of PiDr256)
Type
Default
ARRAY
-
REAL
0.0
STRUCT
-
Value: BOOL
0
ST: BYTE
16#FF
REAL
0.0
STRUCT
-
Value: BOOL
0
ST: BYTE
16#FF
BOOL
1
1
BOOL
1
BOOL
1
ANY
---
SIPART PS2 PA
8.1 SipPS2PA
285

Advertisement

Table of Contents
loading

Table of Contents