The block has the following permissions for the OS1Perm parameter:
Bit
0 - 13
14
15
16 - 31
Simulating signals
Simulation is triggered during runtime in the faceplate's parameter view by clicking on the
"Simulation" button.
You can simulate the following values in the faceplate via an input:
The 4 to 20 mA signal (PV_Out0) in the standard view is specified via the input (SimPV0).
The HART variables (PV_Out1..2) are specified in the standard view via the inputs
(SimPV1..2).
You can simulate the following values via an interconnection in the CFC:
● The level (SimLevLi, Level)
● The volume (SimVolLi, Volume)
● The distance (SimDisLi, Distance)
● The space (SimSpaLi, Space)
● The volume flow (SimVoFLi, VolFlow)
● The temperature (SimTemLi, Temp)
● The custom PV (SimCusLi, CustomPV)
● The custom SV (SimCusLi, CustomSV)
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
1 = Operator can change the limit (PV_In) for the low warning
Not used
1 = Operator can change the value for the high gradient limit for positive gradients
(GradHUpLim)
1 = Operator can change the value for the high gradient limit for negative gradients
(GradHDnLim)
1 = Operator can change the value for the low gradient limit for positive and negative
gradients (GradLLim)
Not used
1 = Operator can activate / deactivate messages with PV_AH_MsgEn
1 = Operator can activate / deactivate messages with PV_WH_MsgEn
1 = Operator can activate / deactivate messages with PV_WL_MsgEn
1 = Operator can activate / deactivate messages with PV_AL_MsgEn
1 = Operator can activate bypass functionality
1 = Operator can deactivate bypass functionality
Not used
Function
Not used
1 = Operator can read the diagnostics values from the device
1 = Operator can read the configuration data from the device
Not used
SITRANS LU HART
17.1 SitrLuHA
785