MultiRanger 200

16.1
MR200
16.1.1

Description of Mr200

Object name (type + number) and family
Type + number: FB 2635
Family: Mr200
Area of application for Mr200
The block is used for the following applications:
● Interface block of the Mr200 module for the user program and visualization
How it works
The Mr200 block prepares the process data received from driver blocks and makes the data
available for further use in the user program and for visualization. Data entered in the faceplate
or via the block inputs is transferred to the Mr200 by means of driver blocks.
Configuration
Use the CFC editor to install the block in a cyclic interrupt OB (OB30 to OB38). The block is also
installed automatically in the startup OB (OB 100). Moreover, to connect the I/O signals it is
imperative to call each of the driver blocks FbMr200 (cyclic data) and PiDr64 (acyclic data) in
the same cyclic interrupt OB and startup OB (OB100) before the Mr200 block is called. The
output structure AcyclData of the PiDr64 block is interconnected to the input with the same
name of the Mr200 block.
The SITRANS Library contains templates for process tag types as an example with an
application scenario for the Mr200 block.
Example of a process tag type: Template of Mr200 (Page 752)
Note
The APL blocks ChkREAL (FC260) and SelST16 (FC369) that are not supplied with the
SITRANS Library are called internally by the Mr200 block. If not yet installed in your project,
copy both blocks from the APL library to your project before you download the project to the
PLC.