9.1 SitransT
Parameter
PV_Meas1*
340
Description
Measured value that is interconnected at
the PV input:
0: Resistance
1: Resistance of channel 2
2: Difference in resistance
3: Average resistance
4: Temperature
5: Temperature of channel 2
6: Difference in temperature
7: Average temperature
8: Voltage
9: Electronics temperature
10: Input 1
11: Input 2
12: Input 1 CJC
13: Input 2 CJC
14: Average of Input 1 and Input 2
15: Difference of Input 1 and Input 2
16: Difference of Input 2 and Input 1
17: Absolute Difference of Input 1 and
Input 2
18: Minimum of Input 2 and Input 1
19: Maximum of Input 2 and Input 1
20: Input 1 and Input 2 as back up
21: Input 2 and Input 1 as back up
22: Average of Input 1 and Input2 as
backup
23: Minimum of Input 2 and Input 1 as
backup
24: Maximum of Input 2 and Input 1 as
backup
25: Not used
(Values 0 to 8 are for TH300, 10 to 24 are
for TH420, 9 and 25 are common to
TH300 and TH420)
Type
BYTE
Function Manual, 05/2019, A5E35351976-11
Default
25