Siemens SITRANS PCS 7 Function Manual page 84

Library
Table of Contents

Advertisement

SITRANS F M MAG 6000
5.1 Mag6T
The following errors can be displayed for this block:
● Error numbers
● Mode switchover error
Overview of error numbers
The I/Os Error1Num (Totalizer 1) and Error2Num (Totalizer 2 or dosing unit) can be used to
output the following error numbers:
Error number
-1
0
12
30
31
32
33
34
35
41
42
84
Meaning of the error number
Predefined value when inserting the block; the block is not executed.
There is no error.
At least one non-plausible limit exists, e.g. the limit for the high alarm is smaller
than that for the high warning
CyclData.Input.VolFlow (volume flow of MAG6000) is not a valid number
CyclData.Input.Tot1VF (count value 1 from MAG6000) is not a valid number
CyclData.Input.Tot2VF (count value 2, or dosing value of MAG6000) is not
a valid number
VolFlow (volume flow) is not a valid number
Tot1VF (count value 1) is not a valid number
Tot2VF (count value 2, or dosing value) is not a valid number
The value for the LocalSetting connection is not within the valid limit of 0, 1 or
3.
LocalSetting = 0 and LocalLi = 1
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11