The disable setting is made with the NoFbkOpen and NoFbkClose parameters for the control
valve.
The disable setting is made with the NoFbkAuxVOpen and NoFbkAuxVClose parameters for
the auxiliary valve.
Time stamp
This block receives a time stamp value via the EventTSIn input parameter. Refer to the
"Functions of EventTs" that are described in the APL Online Help.
Button labels
This block provides the standard "Labeling buttons and texts" function that is described in the
APL Online Help.
Instance-specific text can be configured for the following parameters:
● OpenMan
● CloseMan
8.1.4

Error handling of SipPS2PA

For general information on error handling at all blocks, refer to the "Error handling" section in
the APL Online Help.
The following errors can be displayed for this block:
● Error numbers
● Mode switchover error
● Invalid input signals
Overview of error numbers
The ErrorNum I/O can be used to output the following error numbers:
Error number
-1
0
41
42
51
52
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
Meaning of the error number
Predefined value when inserting the block; the block is not executed.
No active fault
The value of the LocalSetting connection is outside the valid range. Valid values
are 0, 2 and 4
LocalSetting = 0 or LocalSetting = 4 and LocalLi = 1
AutModLi = 1 and ManModLi = 1
OpenAut = 1 and CloseAut = 1
OpenForce = 1 and CloseForce = 1
LocalSetting = 2 or 4 and SimOn = 1
SIPART PS2 PA