Forming the signal status for blocks
This block provides the standard "Form and output signal status for technological blocks"
function that is described in the APL Online Help.
The worst signal status ST_Worst for the block is formed from the following parameters:
● GrpErr.Value
● VolFlow.ST
● Tot1VF.ST/Tot2VF.ST
● Local1Li.ST/Local2Li.ST
● Bal1Local.ST/Bal2Local.ST
● Pos1Local.ST/Pos2Local.ST
● Neg1Local.ST/Neg2Local.ST
● Hold1Local.ST/Hold2Local.ST
● DSrtLocal.ST
● DStpLocal.ST
● DPauseLocal.ST
● DContLocal.ST
● DSP.ST
● DSP_ExtLocal.ST
The respective individual state is only included in the calculation of the worst signal status if the
corresponding component was configured in HW Config.
Release for maintenance
This block provides the standard "Maintenance enable" function that is described in the APL
Online Help.
Configurable reactions using the Feature I/O
The following response features are available for this block at the respective bits of the Feature
I/O:
Bit
Feature
0
Setting the startup characteristics (Page 50)
1
Reaction to the out of service mode (Page 54)
2
Resetting the commands for changing the mode (Page 55)
3
Enabling local operating permission (Page 60)
4
Set switch or button mode (Page 56)
7
Separate delay times for each alarm (Page 52)
8
Read configuration data automatically (Page 57)
9
AUTOHOTSPOT
10
Exiting local mode (Page 58)
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
SITRANS F M MAG 6000
5.1 Mag6T
75