Status word allocation for Status6 parameter
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
Status bit
Parameter
20
1 = Permit is active
21
1 = Protect is active
22
Display for interlocks in block icon
23
1 = Any Interlock is active (Intlock, Permit or Protect)
24
ForceDSrt
25
ForceDStp
26
ForceDPause
27
ForceDCont
28
Reset request in automatic mode
29
Interlocks not released
30
Bypass protection in simulation/local modes
31
Not used
Status bit
Parameter
0
QWronDev
1
External control system fault (CSF)
2
Mode switchover error
3
PV2 is configured as dosing unit
4
PV2 is configured as totalizer
5
PV3 is configured as totalizer
6
PV4 is configured as totalizer
7
Hidden bypass signal in Permit
8
Hidden bypass signal in Intlock
9
Hidden bypass signal in Protect
10
Feature2 Bit 23: Separate bypass signal
11
PV2 input is used
12
PV3 input is used
13
PV4 input is used
14
1 = At least one PV1 message is released
15
1 = At least one PV2 message is released
16
1 = At least one PV3 message is released
17
1 = At least one PV4 message is released
18
"Custody transfer mode" is active
19
PV2 : Current totalizer command 1 = Totalize
20
PV3 : Current totalizer command 1 = Totalize
21
PV4 : Current totalizer command 1 = Totalize
22
Bypass Activation on QC in BlockIcon
23
Mode switchover error
24
BypassAct.Value
25
PV2: Current totalizer command 1 = Hold
SITRANS FC430 PA