SITRANS LU HART
17.1 SitrLuHA
Parameter
Description
Current volume flow
Flow
Current sensor temperature
Temp
Current custom value PV
CustomPV
Current custom value SV
CustomSV
Limit sensor PV_In:
PV_AH_Act
1 = Alarm (high) active.
You can change the response for this parameter
by setting Feature bit 28 (deactivate switching
points) and Feature bit 29 (high/low signal limit
violation) accordingly.
Limit sensor PV_In:
PV_WH_Act
1 = Warning (high) active.
You can change the response for this parameter
by setting Feature bit 28 (deactivate switching
points) and Feature bit 29 (signal limit violation)
accordingly.
Limit sensor PV_In:
PV_WH_Act
1 = Warning (low) active.
You can change the response for this parameter
by setting Feature bit 28 (deactivate switching
points) and Feature bit 29 (signal limit violation)
accordingly.
Limit sensor PV_In:
PV_AL_Act
1 = Alarm (low) active.
You can change the response for this parameter
by setting Feature bit 28 (deactivate switching
points) and Feature bit 29 (signal limit violation)
accordingly.
1 = Group signal is active
SumMsgAct
Measuring range of 4 to 20 mA signal
ScaleOut
Unit of measure for process value
PV_InUnit
Unit for level
LevelUnit
Unit for volume
VolUnit
798
Type
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : BOOL
● ST: BYTE
STRUCT
● Value : BOOL
● ST: BYTE
STRUCT
● Value : BOOL
● ST: BYTE
STRUCT
● Value : BOOL
● ST: BYTE
STRUCT
● Value : BOOL
● ST: BYTE
STRUCT
● High : REAL
● Low: REAL
INT
INT
INT
Function Manual, 05/2019, A5E35351976-11
Default
-
● 0.0
● 16#80
-
● 0.0
● 16#80
-
● 0.0
● 16#80
-
● 0.0
● 16#80
-
● 0
● 16#80
-
● 0
● 16#80
-
● 0
● 16#80
-
● 0
● 16#80
-
● 0
● 16#80
-
● 0.0
● 0.0
0
0
0
SITRANS Library for PCS 7