SITRANS T
9.1 SitransT
Associated value
3
4
5
6
7
8
9
10
The associated values 4 ... 8 are allocated to the parameters ExtVa104 ... ExtVa108 and can
be used. Additional information is available in the "Process Control System PCS 7 -
Engineering System" manual.
9.1.6

I/Os of SitransT

Input parameters
Parameter
SlotHart
DevType
PV_In
PV
SV
TV
QV
PV_Hyst*
332
Block parameters
BatchID
ExtVa104
ExtVa105
ExtVal06
ExtVa107
ExtVa108
Reserved
Reserved
Description
Slot number of the Sitrans TH300/TH420
within the AI module in the ET200M from
HW Config
Device type of Sitrans T
0: No Device
1: Sitrans TH/R300
2: Sitrans TH/Rx20
Process value (4 to 20 mA signal)
First HART variable (primary variable)
Second HART variable (secondary vari‐
able)
Third HART variable (tertiary variable)
Fourth HART variable (quaternary varia‐
ble)
Hysteresis for PV alarm and warning lim‐
its
Type
INT
INT
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
STRUCT
● Value : REAL
● ST: BYTE
REAL
Function Manual, 05/2019, A5E35351976-11
Default
0
1
-
● 0.0
● 16#80
-
● 0.0
● 16#80
-
● 0.0
● 16#80
-
● 0.0
● 16#80
-
● 0.0
● 16#80
0.0
SITRANS Library for PCS 7

Advertisement

Table of Contents
loading

Table of Contents