Siemens SITRANS PCS 7 Function Manual page 566

Library
Table of Contents

Advertisement

SITRANS FC430 PA
13.1 SiFC43PA
Parameter
PV_Meas1
PV_Meas2
PV_Meas3..4
LagTime
DSP_LiOp
566
Description
Measurement of Process Value 1:
0: Mass flow
1: Density
2: Process media temperature
5: Volume flow
6: Fraction A
7: Fraction B
8: Fraction A %
9: Fraction B %
10: Corrected volume flow
11: Sensor frame temperature
14: Not used
Measurement of Process Value 2:
0: Mass flow
1: Density
2: Process media temperature
3: Totalizer 1
4: Totalizer 2
5: Volume flow
6: Fraction A
7: Fraction B
8: Fraction A %
9: Fraction B %
10: Corrected volume flow
11: Sensor frame temperature
12: Totalizer 3
13: Control commands
14: Not used
15: Dosing (only PV_Meas2)
Measurement of Process Value 3 and 4:
0: Mass flow
1: Density
2: Process media temperature
3: Totalizer 1
4: Totalizer 2
5: Volume flow
6: Fraction A
7: Fraction B
8: Fraction A %
9: Fraction B %
10: Corrected volume flow
11: Sensor frame temperature
12: Totalizer 3
13: Control commands
14: Not used
Delay time [s]
Dosing unit: Select setpoint source (internal/
external):
● 1 = Via interconnection
● 0 = Via operator
Type
Default
BYTE
-
BYTE
-
BYTE
-
REAL
10.0
STRUCT
-
● Value : BOOL
● 0
● ST: BYTE
● 16#80
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11

Advertisement

Table of Contents
loading

Table of Contents