Sipps2Ha Messaging - Siemens SITRANS PCS 7 Function Manual

Library
Table of Contents

Advertisement

SIPART PS2 HART
7.1 SipPS2HA
Overview of error numbers
The ErrorNum I/O can be used to output the following error numbers:
Error number
-1
0
41
42
51
52
Mode switchover error
This error can be output by the block, see the "Error handling" section in the APL Online Help.
Invalid input signals
This error can be output by the block, see the "Error handling" section in the APL Online Help.
7.1.5

SipPS2HA messaging

Messaging
The following messages can be generated for this block:
● Process control error
● Process messages
● Instance-specific messages
Process control error
The following control system fault messages can be output:
Message
instance
MsgEvId1 SIG1
212
Meaning of the error number
Predefined value when inserting the block; the block is not executed.
No active fault
The value of the LocalSetting connection is outside the valid range. Valid values
are 0, 2 and 4
LocalSetting = 0 or LocalSetting = 4 and LocalLi = 1
AutModLi = 1 and ManModLi = 1
OpenAut = 1 and CloseAut = 1
OpenForce = 1 and CloseForce = 1
LocalSetting = 2 or 4 and SimOn = 1
Message
Message class
identifier
AS process control message - fault
SIG6
AS process control message - fault
Event
$$BlockComment$$ Feed‐
back error
$$BlockComment$$ External
error has occurred
SITRANS Library for PCS 7