SITRANS P
10.1 SitransP
Parameter
Description
Error0Num
Output of current error number for the 4 to 20 mA
signal. For error numbers that can be output by this
block, see Error handling of SitransP (Page 374)
Error1Num
Output of current error number for the first HART
variable (primary variable). For error numbers that
can be output by this block, see Error handling of
SitransP (Page 374)
Error2Num
Output of current error number for the second
HART variable (secondary variable). For error num‐
bers that can be output by this block, see Error
handling of SitransP (Page 374)
Error3Num
Output of current error number for the third HART
variable (tertiary variable). For error numbers that
can be output by this block, see Error handling of
SitransP (Page 374)
Error4Num
Output of current error number for the fourth HART
variable (quaternary variable). For error numbers
that can be output by this block, see Error handling
of SitransP (Page 374)
MsgErr1
1 = Message error 1 (output ERROR of first
ALARM_8P)
MsgStat1
Message status 1 (output ERROR of first
ALARM_8P)
MsgAckn1
Message acknowledgment status 1 (output STA‐
TUS of first ALARM_8P)
MsgErr2
1 = Message error 2 (output ERROR of second
ALARM_8P)
MsgStat2
Message status 2 (output ERROR of second
ALARM_8P)
MsgAckn2
Message acknowledgment status 2 (output STA‐
TUS of second ALARM_8P)
MsgErr3
1 = Message error 3 (output ERROR of third
ALARM_8P)
MsgStat3
Message status 3 (output ERROR of third
ALARM_8P)
MsgAckn3
Message acknowledgment status 3 (output STA‐
TUS of third ALARM_8P)
LxScale
Limit sensor x:
(x= 1,2,3)
Maximum and minimum values for the alarm and
warning limits
396
Type
Default
INT
-1
INT
-1
INT
-1
INT
-1
INT
-1
BOOL
0
WORD
16#0000
WORD
16#0000
BOOL
0
WORD
16#0000
WORD
16#0000
BOOL
0
WORD
16#0000
WORD
16#0000
STRUCT
-
● AH_High: REAL
● 0.0
● AH_Low: REAL
● 0.0
● WH_High: REAL
● 0.0
● WH_Low: REAL
● 0.0
● Hyst_High: REAL
● 0.0
● AL_High: REAL
● 0.0
● AL_Low: REAL
● 0.0
● WL_High: REAL
● 0.0
● WL_Low: REAL
● 0.0
SITRANS Library for PCS 7