(7) Display current control signals
Only if dosing is configured:
● "Enable":
● "Protection":
0 = Protective interlocking is effective; once the interlocking condition has disappeared, you
will have to reset the block
● "Interlock":
interlocking condition has disappeared
(8) Display current control signals
This area shows the most important parameters for this block with the current selection:
Dosing unit:
● "Local dosing": 1 = Control signal for "Local mode" (LocalSVLi) is enabled
● "Local start": 1 = Block is started in "Local mode"
● "Local pause": 1= Dosing paused in "Local mode"
● "Local resume": 1 = Dosing is resumed in "Local mode"
● "Local stop": 1 = Dosing is stopped in "Local mode"
Totalizer:
● "Local tot": 1 = Totalizer is operated in "Local mode"
● "Local P./N. tot": 1 = Totalizer counts positive and negative in "Local mode"
● "Local pos. tot": 1 = Totalizer counts positive in "Local mode"
● "Local Neg. tot": 1 = Totalizer counts negative in "Local mode"
● "Local Neg. Hold": 1 = Totalizer is in hold in "Local mode"
(9) Change to second preview
The second part of the two-part preview of the faceplate can be selected here.
(10) Button for switching to the standard view of any faceplate
Use this navigation button to open the standard view of a block configured in the engineering
system. The visibility of this navigation button depends on the configuration in the engineering
system (ES).
You can find more information on this in the section "Opening additional faceplates" in the APL
Online Help.
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
0 = No OS activation enable for the motor
1 = Enable for "Start" / "Stop" from the neutral position
1 = Good state
0 = Interlocking without reset is active; you can operate the block without reset once the
1 = Good state
SITRANS FC430 PA
13.1 SiFC43PA
619