I/Os Of Mr200Dia - Siemens SITRANS PCS 7 Function Manual

Library
Table of Contents

Advertisement

MultiRanger 200
16.3 Mr200Dia
Use in CFC
The following actions are executed automatically with the "Generate module drivers" CFC
function:
● The Mr200Dia block is installed in its runtime group downstream of the OB_DIAG1 block
runtime group in the above-mentioned OBs.
● The logical base address LADDR and the diagnostic address DADDR are configured.
● The SUBN_TYP input parameter is set to 1 if the Multiranger-200 is connected to a CPU via
CP (external DP interface), otherwise to 0.
● The inputs SUBN1_ID and SUBN2_ID are configured
● The inputs RACKF, SUBN1ERR and SUBN2ERR are interconnected to the corresponding
outputs of the OB_DIAG1 block.
● The outputs QMODF, QUALITY and OMODE are interconnected to the
MOD_PAX0/MOD_PAL0 block.
16.3.2

I/Os of Mr200Dia

Input parameters
Parameter
LADDR
DADDR
RACKF
SUBN_TYP
SUBN1_ID
SUBN1_ID
SUBN1ERR
SUBN2ERR
In/out parameters
Parameter
ACC_ID
Output parameters
Parameter
QERR
QMODF
QRACKF
RACK1ERR
774
Description
Logical address of module
Diagnostic address of module
1 = DP slave failure (rack fault)
1 = external DP interface
ID of primary subnet
ID of redundant subnet
1 = slave 1 failure
1 = slave 2 failure
Description
1 = accept MODE settings
Description
1 = error
1 = module failure
1 = rack failure
1 = DP slave system failure (primary)
Type
Default
INT
0
INT
0
BOOL
0
BOOL
0
BYTE
16#FF
BYTE
16#FF
BOOL
0
BOOL
0
Type
Default
BOOL
0
Type
Default
BOOL
0
BOOL
0
BOOL
0
BOOL
0
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11