SIPART PS2 PA
8.1 SipPS2PA
(6) Manipulated variable operating range (MV)
In this area, you can enter the limits for the manipulated variable operation range. Refer to the
"Changing values" section in the APL Online Help.
You can change the following limits:
● "H range": Range limit high
● "L range": Range limit low
(7) Message suppression/delays
The message suppression indicates whether suppression of the associated message is
activated in the AS block using the xx_MsgEn parameter. The output of messages is not
suppressed when the block is installed (all xx_MsgEn parameters are set to 1 by default).
Messages can only be output if limit monitoring of the additional analog value has been enabled.
Alarm delays are also displayed in this state; refer to the "Application of alarm delays" section
in the APL Online Help.
(8) Suppress messages
You can activate/deactivate messages by selecting the check mark.
312
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11