Siemens SITRANS PCS 7 Function Manual page 685

Library
Table of Contents

Advertisement

18
19
20
21
22
23
24
25
26
27
28
29
30 - 31
The block has the following permissions for the OS1Perm parameter:
Bit
0 - 13
14
15
16 - 31
Simulating signals
Simulation is triggered during runtime in the faceplate's parameter view by clicking on the
"Simulation" button.
You can simulate the following values in the faceplate via an input:
The 4 to 20 mA signal (PV_Out0) in the standard view is specified via the input (SimPV0).
The HART variables (PV_Out1..4) are specified in the standard view via the inputs
(SimPV1..4).
You can simulate the following values via an interconnection in the CFC:
● The level (SimLevLi, Level)
● The volume (SimVolLi, Volume)
● The distance (SimDisLi, Distance)
● The space (SimSpaLi, Space)
The Level, Volume, Distance and Space outputs are simulated in accordance with the
module configuration when simulation is carried out via the faceplate. The simulation value of
the 4 to 20 mA signal has a higher priority than the value of the first HART auxiliary variable PV.
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
1 = Operator can change the limit (PV_In) for the low warning
Not used
1 = Operator can change the value for the high gradient limit for positive gradients
(GradHUpLim)
1 = Operator can change the value for the high gradient limit for negative gradients
(GradHDnLim)
1 = Operator can change the value for the low gradient limit for positive and negative
gradients (GradLLim)
Not used
1 = Operator can activate / deactivate messages with PV_AH_MsgEn
1 = Operator can activate / deactivate messages with PV_WH_MsgEn
1 = Operator can activate / deactivate messages with PV_WL_MsgEn
1 = Operator can activate / deactivate messages with PV_AL_MsgEn
1 = Operator can activate bypass functionality
1 = Operator can deactivate bypass functionality
Not used
Function
Not used
1 = Operator can read the diagnostics values from the device
1 = Operator can read the configuration data from the device
Not used
SITRANS LR HART
15.1 SitrLRHA
685