Activating Know-How Protection - Siemens SINAMICS Series Operating Instructions Manual

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Procedure
1. Use parameter p7763 to define the required number of parameters for the exception list.
You can enter a maximum of 500 parameters in the exception list.
2. Execute the "Load to PG" function.
Parameter p7764 is adapted in the expert list according to the setting in p7763. Indices
are inserted or deleted depending on the setting.
3. In parameter p7764[0...n], assign the individual indices of p7763 to the required
parameter numbers.
4. Transfer the changes to the Control Unit so that they can become effective.
Note
Parameters of the exception list are not checked
The Control Unit does not check which parameters you include or delete in the exception list.
Absolute know-how protection
By removing parameter p7766 from the exception list of p7764[0] = 0, you prevent any
access at all to the data of the Control Unit and your project settings. It is then impossible to
read or change the protected data. The know-how protection and the copy protection can no
longer be canceled or deactivated.

Activating know-how protection

1. Connect the Control Unit to the programming device.
2. Call STARTER.
3. Open your project.
4. Establish a connection to the target device.
5. Select the required drive unit in the project navigator of your STARTER project.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Descriptions of functions
10.38 Write and know-how protection
675