Commissioning
8.5 Commissioning with the STARTER commissioning tool
Note
For 2Q devices, the rated DC voltage of the SINAMICS DCM specified in the technical data,
can only be achieved if the α
to reach the rated motor voltage (p50101[D]), the α
⇒ If you select speed-dependent current limiting, then in another setting form you can set the
required values (parameters p50104 ... p50109).
⇒ Click Next >
NOTICE
Ensure protection against overload
The data are very important for protecting against overload and must be entered correctly.
304
limit (p50150) is set to 5°. The factory setting is 30°. In order
G
G
limit must also be changed to 5°.
SINAMICS DCM DC Converter