Maintenance
11.2 Replacing components
Replacing fans in 400 to 850 A devices
1. Remove the front cover of the SINAMICS DC MASTER
2. Withdraw the connector for the fan sensor
3. Withdraw the connector for the fan power supply
4. Loosen the screws
5. Withdraw the fan module towards the front
6. Insert the new fan module and tighten the fastening screws (tightening torque 1.5 Nm), reinsert
the connector and reattach the front cover
Figure 11-5
694
(tool: Torx T20 screwdriver)
Replacing fans in 400 - 850 A devices
Operating Instructions, 12/2018, A5E34763375A
SINAMICS DCM DC Converter