I&M parameter
Format
designation
I&M 3:
Visible
DESCRIPTOR
string
I&M 4:
Octet
SIGNATURE
string
The I&M data sets 1...3 are stored permanently in the parameters p8806...p8808. Essential
properties of these 3 parameters:
● They can be displayed in the STARTER expert list.
● The SINAMICS "Reset parameter" (p0976 = 1, p0970 = 1) function does not have any
effect on the content of parameters.
● I&M data sets are not changed when the alternative parameter sets are stored or loaded.
The transfer of parameter sets between a memory card and non-volatile device memory
does not have any effect on the I&M data sets.
Overview of important parameters (see SINAMICS DCM List Manual)
• p8806[0...53]
• p8807[0...15]
• p8808[0...53]
• r8809[0...53]
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Size/
Initialization
octets
54
Space
0x20...0x20
54
Space
0x00...0x00
Identification and Maintenance 1
Identification and Maintenance 2
Identification and Maintenance 3
Identification and Maintenance 4
10.5 Communication via PROFINET IO
SINAMICS
Meaning
parameters
p8808[0...53]
Text with any comments or notes.
r8809[0...53]
The parameter is automatically populated by
the system, in which case it contains a
functional check signature for the change
tracking with Safety Integrated. The check
signature has the following format:
The first four octets (0...3) contain the
content of parameter r9781 index 0:
"SI change monitoring checksum
(Control Unit)".
The second four octets (4...7) contain the
content of parameter r9782 index 0:
"SI change monitoring time stamp
(Control Unit)".
The remainder (octets 8...53) contains
zeroes.
Descriptions of functions
511