Figure 8-26
Entering encoder data – Pulse encoder via SMC30
⇒ Select the encoder connection (SUB-D /terminal).
⇒ Enter the required encoder data.
⇒ Click on OK
NOTICE
Material damage when selecting the incorrect encoder supply voltage
Once the encoder has been commissioned, the supply voltage (5 V / 13.5 - 30 V) set for the
encoder is activated on the SMC30 Module. If a 5 V encoder is connected and the supply
voltage has not been set correctly, the encoder may be damaged.
• Set the correct supply voltage for the connected encoder.
⇒ Click on Next >
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
8.5 Commissioning with the STARTER commissioning tool
Commissioning