Descriptions of functions
10.34 Diagnostics
Sequence of a multiple trace
1. A multiple trace is started just like a conventional single trace using the STARTER
"Trace" screen form.
2. The multiple trace component saves the measurement result after the trigger condition
has occurred and the trace data has been completely recorded.
3. The single trace that has actually been completed is now automatically restarted from the
multiple trace component. In this case, the same trace configuration (trigger condition,
recording cycle, etc. ) is used as before. The trace buffer of the previous single trace is
emptied in the process.
Trace status
The status of the multiple trace is displayed in the screen form (red frame):
Figure 10-96 Trace status in STARTER
Startup trace
A startup trace basically consists of a conventional single trace with all of its configuration
options (number of channels, sampling depth, recording cycle, etc.). With the appropriate
configuration, a startup trace is automatically active after a drive restarts.
646
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A