Operation
9.3 Controlling via the AOP30 operator panel
Settings: Menu – Commissioning/Service – AOP settings – Control settings
Save LOCAL mode (factory setting: Yes)
● Yes: The "LOCAL" or "REMOTE" operating state is saved when the power supply is
switched off and restored when the power supply is switched back on.
● No: The "LOCAL" or "REMOTE" operating state is not saved. "REMOTE" is activated
when the power supply is switched on.
OFF in REMOTE (factory setting: No)
● Yes: The OFF key functions in REMOTE mode even if the drive is being controlled by
external sources (PROFIBUS, customer terminal strip, NAMUR terminal strip).
WARNING: This function is not an EMERGENCY STOP function.
● No: The OFF key only functions in LOCAL mode.
LOCAL/REMOTE also during operation (factory setting: No)
● Yes: You can switch between LOCAL and REMOTE when the drive is switched on (motor
is running).
● No: Before switching to LOCAL, a check is carried out to determine whether the drive is in
the "Operation" status. If it is, switchover is prevented and the error message "Local
mode during operation not possible" is output. Before the system switches to REMOTE,
the drive is switched off and the setpoint is set to 0.
9.3.7.2
ON key/OFF key
ON key: Active in LOCAL if no operator inhibit lock is activated
OFF key: Always active in LOCAL; active in REMOTE under certain conditions (if the system
setting "OFF in REMOTE" is set to "Yes")
OFF key acts as
● OFF1: Ramp-down on the down ramp (p50303)
At speed 0: Disconnection (only if line contactor is present)
● OFF2: Immediate pulse inhibit, motor coasts down
● OFF3: Ramp-down on the quick stop ramp (p50296)
Factory setting: OFF1
394