Error
Meaning
value
0x6B
Write access for the enabled
controller.
0x6C
Parameter %s [%s]: Unknown unit.
0x6D
Parameter %s [%s]: Write access
only in the commissioning state,
encoder (p0010 = 4).
0x6E
Parameter %s [%s]: Write access
only in the commissioning state,
motor (p0010 = 3).
0x6F
Parameter %s [%s]: Write access
only in the commissioning state,
power unit (p0010 = 2).
0x70
Parameter %s [%s]: Write access
only in the quick commissioning
mode (p0010 = 1).
0x71
Parameter %s [%s]: Write access
only in the ready mode (p0010 = 0).
0x72
Parameter %s [%s]: Write access
only in the commissioning state,
parameter reset (p0010 = 30).
0x73
Parameter %s [%s]: Write access
only in the commissioning state,
Safety (p0010 = 95).
0x74
Parameter %s [%s]: Write access
only in the commissioning state, tech.
application/units (p0010 = 5).
0x75
Parameter %s [%s]: Write access
only in the commissioning state
(p0010 not equal to 0).
0x76
Parameter %s [%s]: Write access
only in the commissioning state,
download (p0010 = 29).
0x77
Parameter %s [%s] must not be
written during download.
0x78
Parameter %s [%s]: Write access
only in the commissioning state, drive
configuration (device: p0009 = 3).
0x79
Parameter %s [%s]: Write access
only in the commissioning state,
define drive type (device: p0009 = 2).
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
10.3 Communication according to PROFIdrive
Remark
Write access is possible while the device is in the "Controller
enable" state.
Pay attention to the parameter attribute "changeable" in the
SINAMICS DCM List Manual (C1, C2, U, T).
Descriptions of functions
Additional
info