Siemens SINAMICS Series Operating Instructions Manual page 708

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Applications
12.3 Use of the SINAMICS DCM in galvanizing and dip-painting plants
HTL encoder, unipolar, with zero signal
Figure 12-2
12.3
Use of the SINAMICS DCM in galvanizing and dip-painting plants
2Q devices are used when using the SINAMICS DCM in galvanizing, dip-painting or similar
plants.
2Q devices have a thyristor bridge in B6 circuit. In this power unit topology, the output
voltage of the SINAMICS DCM is partly negative for firing angles between 60° and 120°. In
order to ensure that no negative voltages are present at the load, i.e. at the galvanizing and
paint tanks, an external freewheeling diode is usually installed on the DC side for these
applications. This is not part of the SINAMICS DCM, but rather is installed in the control
cabinet.
Figure 12-3
Make sure that in this case, the current actual value sensing in the converter only measures
part of the load current, i.e. the current through the converter, not the freewheeling current.
This means that the SINAMICS DCM cannot control the load current.
706
Unipolar incremental encoder
SINAMICS DCM, 2Q device with external freewheeling diode
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A

Advertisement

Table of Contents
loading

Table of Contents