Note
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter
(BI: Inhibit master control).
9.3.7.8
Acknowledging errors via the AOP
Settings: MENU – Commissioning / Service – AOP Settings – Control Settings
Acknowledge fault from the AOP (factory setting: Yes)
● Yes: Errors can be acknowledged via the AOP.
● No: Faults cannot be acknowledged via the AOP.
9.3.7.9

Timeout monitoring

In "LOCAL" mode or if "OFF in REMOTE" is active, the drive is shut down after 1 s if the data
cable between the AOP and drive is disconnected.
9.3.7.10
Operator inhibit lock/Parameters disable
Operator inhibit lock/Parameters disable
To prevent the control keys from being operated and parameters from being changed
unintentionally, you can activate an operator inhibit lock/parameters disable using a key-
operated pushbutton. Two key icons appear at the top right of the display when these safety
inhibits are enabled.
Table 9- 12
Inhibit type
No safety inhibit
Operator lock
Parameter disable
Operator inhibit lock + parameters disable
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Operator inhibit lock/parameters disable
9.3 Controlling via the AOP30 operator panel
Online mode
Operation
Offline mode
397