Siemens SINAMICS Series Operating Instructions Manual page 491

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Assigning the IP address and name for the PROFINET interface of the drive unit
With STARTER, you can assign an IP address and a name to the PROFINET interface
(e.g. CBE20) of the drive unit. The following steps are required:
1. Connect the programming device via a Crosslink-Ethernet cable with the CBE20, inserted
in the CUD.
2. Switch on the Control Unit.
3. Open STARTER.
4. Call the menu "Project > Accessible nodes" or click the "Accessible nodes" icon.
– The search is performed for available nodes connected to PROFINET.
– The Control Unit is identified and displayed under "Accessible nodes" as the bus node
5. Right-click the bus node entry to open the shortcut menu "Edit Ethernet node ...".
– In the selection window that opens "Edit Ethernet node" you will also see the MAC
6. Under "Set IP configuration", enter the IP address that you selected (e.g. 169.254.11.33)
and the subnet mask (e.g. 255.255.0.0).
7. Click the "Set IP configuration" button.
– The data transfer is confirmed.
8. Click the "Update" button.
– The bus node is identified as a drive unit.
– The address and the type are specified.
In the "Edit Ethernet node" selection window you can also assign a device name to the
drive unit that has been detected.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
with the IP address 0.0.0.0, without any type information.
Figure 10-37 Bus nodes found