Siemens SINAMICS Series Operating Instructions Manual page 431

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Bit
Name
13
Transmit absolute value
cyclically
14
Parking encoder
15
Encoder fault
Encoder 1 actual position value 1 (G1_XIST1)
● Resolution: Encoder lines ∙ 2n
n: Fine resolution, no. of bits for internal multiplication
The fine resolution is specified via p0418.
● Used to transfer the cyclic actual position value to the controller.
● The transferred value is a relative, free-running actual value.
● Any overflows must be evaluated by the master controller.
Figure 10-6
● Encoder lines of incremental encoder
– For encoders with sin/cos 1Vpp:
● After power-up: Gx_XIST1 = 0
● An overflow in Gx_XIST1 must be viewed by the master controller.
● There is no modulo interpretation of Gx_XIST1 in the drive.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Signal status, description
1
Acknowledgement for Gn_STW.13 (request absolute value cyclically)
Note:
Cyclic transmission of the absolute value can be interrupted by a function
with higher priority.
See Gn_XIST2
0
No acknowledgement
1
Parking encoder active (i.e. parking encoder switched off)
0
No active parking encoder
1
Error from encoder or actual-value sensing is active.
Note:
The error code is stored in Gn_XIST2.
0
No error is active.
Subdivision and settings for Gx_XIST1
Encoder lines = No. of sinusoidal signal periods
Descriptions of functions
10.3 Communication according to PROFIdrive
429