Note
Incorrect temperature measured values as a result of cables with an excessively high
resistance
An excessively long cable length or an excessively small cable cross-section can falsify the
temperature measurement (for a PT100, 10 Ω cable resistance can falsify the measurement
result by 10%). As a consequence, excessively high measured values are output, which
could lead to the motor being unnecessarily tripped prematurely.
• Use only cable lengths ≤ 300 m.
• For cable lengths >100 m, use cables with a cross-section of ≥1 mm
7.6.4
Connection examples
Figure 7-31
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Connecting a PT100/PT1000 with 2x2, 3 and 4-wires to the temperature sensor inputs
X53x of Terminal Module TM150
Additional system components
7.6 Terminal Module TM150
.