Adapting unit data and entering motor data
Figure 8-21
Motor data
⇒ Adapt the rated armature DC current for the unit by making a setting at p50076[0] (in %) or
p50067 if:
Maximum armature current < 0.5 × rated armature DC current for the unit
⇒ Adapt the rated armature DC current field for the unit by making a setting at p50076[1]
(in %) if:
Maximum field current < 0.5 × rated field DC current for the unit
⇒ Enter the actual supply voltage for the unit p50078.
⇒ Here, enter the motor data as a stamped on the motor rating plate.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
8.5 Commissioning with the STARTER commissioning tool
Commissioning
303