Siemens SINAMICS Series Operating Instructions Manual page 278

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Commissioning
8.3 Commissioning using the BOP20 operator panel
Note
For 2Q devices, the rated DC voltage of the SINAMICS DCM specified in the technical data,
can only be achieved if the α
to reach the rated motor voltage (p50101[D]), the α
〈5〉Data for actual speed value acquisition
〈5.1〉Operation with analog tachometer
p50083[D] = 1 The actual speed value comes from the "Main actual value" (r52013)
p50741[D]
p2000
〈5.2〉Operation with incremental encoder
p50083[D] = 2 The actual speed value comes from an incremental encoder (r0061)
p0400[0]
p2000
276
limit (p50150) is set to 5°. The factory setting is 30°. In order
G
channel (terminals XT1-103, XT1-104)
Tachometer voltage at maximum speed (– 270.00 to +270.00 V)
Remark:
The value set here determines the 100% speed for the closed-loop speed
control.
Speed in rpm for tachometer voltage set on p50741[0]
Comment 1:
Parameter p2000 is used to convert from a "physical speed" (rpm) into a
"relative speed" (%) and vice versa.
This conversion is required for:
• Speed setpoint input via the control panel in STARTER
• Speed setpoint input via the operating screen form at the AOP30
• Calculation of display values r0020, r0021, r0060 and r0063
Remark 2:
Parameter p2000 and parameters r0020, r0021, r0060 and r0063 are not
data-set dependent. This is the reason why the physical speed can only be
displayed correctly for one data set (DDS).
connected to terminal block X177.
Encoder type selection
Speed in rpm at 100% speed
Remark:
The value set here determines the 100% speed for the closed-loop speed
control.
limit must also be changed to 5°.
G
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A