Connecting
6.9 Assignment of terminals and connectors
Table 6- 24
Terminal type, power connections for devices of 60 A and above
Devices
60 A - 210 A
280 A
400 A - 450 A
600 A
720 A - 850 A
900 A - 1200 A
1500 A - 2000 A
170
Data
1U1, 1V1, 1W1: 3 x 20 mm aluminum busbar, through hole for M8
1C1, 1D1: 5 x 20 mm aluminum busbar, through hole for M8
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1, 1C1, 1D1: 2 × 95 mm
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 13 Nm
Tightening torque for protective conductor: 25 Nm
1U1, 1V1, 1W1: 3 x 20 mm copper busbar, through hole for M8
1C1, 1D1: 5 x 20 mm copper busbar, through hole for M8
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1, 1C1, 1D1: 2 × 95 mm
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 13 Nm
Tightening torque for protective conductor: 25 Nm
1U1, 1V1, 1W1: 5 x 30 mm aluminum busbar, through hole for M10
1C1, 1D1: 5 x 35 mm aluminum busbar, through hole for M10
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1: 2 × 150 mm
1C1, 1D1: 2 × 185 mm
2
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 25 Nm
Tightening torque for protective conductor: 50 Nm
1U1, 1V1, 1W1: 5 x 30 mm copper busbar, through hole for M10
1C1, 1D1: 5 x 35 mm copper busbar, through hole for M10
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1: 2 × 150 mm
1C1, 1D1: 2 × 185 mm
2
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 25 Nm
Tightening torque for protective conductor: 50 Nm
1U1, 1V1, 1W1, 1C1, 1D1: 5 x 60 mm copper busbar, through hole for M12
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1, 1C1, 1D1: 4 × 150 mm
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 44 Nm
Tightening torque for protective conductor: 50 Nm
1U1, 1V1, 1W1, 1C1, 1D1: 6 x 80 mm copper busbar, M12 insert nut
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1: 4 × 150 mm
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 44 Nm
Tightening torque for protective conductor: 60 Nm
1U1, 1V1, 1W1: 10 x 120 mm aluminum busbar, through hole for M12
1C1, 1D1: Aluminum busbar, cross-section 60 x 10 mm / 323 mm wide, insert nut M12
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1: 6 × 240 mm
1C1, 1D1: 8 × 240 mm
2
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 44 Nm
Tightening torque for protective conductor: 60 Nm
2
2
2
2
2
2
2
Operating Instructions, 12/2018, A5E34763375A