Siemens SINAMICS Series Operating Instructions Manual page 601

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Connection
Figure 10-74 Connection to a single-phase line supply
The converter is connected to the line supply (one phase and the neutral conductor, e.g.
230 V or two phase conductors of a three-phase line supply, e.g. 400 V) via terminals 1U1
and 1V1. Connection 1W1 remains free.
It is mandatory that a single-phase line reactor or a transformer with 4% u
only supplies the DC converter involved.
Commutating reactor and transformer should be selected according to the rated motor
current of the armature circuit.
In this B2 circuit, the line current is equal to the DC current in the armature circuit. All of the
other line-side drive components should be dimensioned according to this. Further, due to
the higher current ripple when compared to six-pulse operation, a smoothing reactor must be
provided in the DC circuit. Please contact the motor manufacturer when dimensioning the
smoothing reactor.
Parameterization
Selecting operation on a single-phase line supply with p51799 = 1
The high current ripple in this mode causes ripple in the actual speed. For smooth
speed control, it is recommended to set the actual speed smoothing to approx. 10 ms
(p50200 = 10 ms)
Derating
When selecting operation on a single-phase line supply, the rated DC current (r50072[1]) is
automatically reduced to 67% of the value for 3-phase operation. The reason for this is the
uneven distribution of the current in the thyristors in the power unit of the drive converter.
As a consequence, the rated output voltage is also reduced. See also Chapter "Technical
data (Page 39)".
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Descriptions of functions
10.27 Operation on a single-phase line supply
is provided, which
k
599

Advertisement

Table of Contents
loading

Table of Contents