A B B M EA S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N | O I / T T H 3 0 0 - E N R E V . G
TTH300
Head-mount temperature transmitter
Introduction
TTH300
The TTH300 is available with the HART, PROFIBUS
PA and FOUNDATION Fieldbus communications
protocols.
The transmitter has global approvals for
explosion protection up to zone 0.
The TTH300 implements various NAMUR
recommendations, including NE 89 and NE 107.
Safety-relevant applications up to SIL 3
(redundant) are supported in accordance with
IEC 61508.
Temperature transmitter for all
communications protocols.
Redundancy thanks to two inputs.
Measurement made easy
Additional Information
Additional documentation on TTH300 is available for
download free of charge at
www.abb.com/temperature.
Alternatively simply scan this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB TTH300

  • Page 1 Redundancy thanks to two inputs. Measurement made easy — Introduction Additional Information TTH300 The TTH300 is available with the HART, PROFIBUS Additional documentation on TTH300 is available for PA and FOUNDATION Fieldbus communications download free of charge at protocols. www.abb.com/temperature.
  • Page 2 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Table of contents Safety ................ 5 Transport and storage ........... 19 General information and instructions ......... 5 Inspection ................19 Warnings .................. 5 Transporting the device ............19 Intended use ................6 Storing the device ..............19 Improper use ................
  • Page 3: Table Of Contents

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Input - thermocouples / voltages........25 Parameter description HART® (for HART®-devices to SW-Rev. 1.03) ........42 Types ................. 25 Voltages ................25 Menu: Device Setup ............42 Connection lead ............... 25 Menu: Device Info ............45 Detection of sensor wire break in accordance with Menu: Display ..............
  • Page 4 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 12 Maintenance ............72 Safety instructions ............... 72 Cleaning ................. 72 13 Repair ............... 72 Safety instructions ............... 72 Returning devices ..............72 14 Recycling and disposal ........... 73 15 Specification ............73 16 Additional documents ..........
  • Page 5 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 1 Safety General information and instructions Warnings The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
  • Page 6 / or theft of data or information. • When using as a SIL-device in safety-relevant applications, ABB Automation Products GmbH and its affiliates are not liable the SIL Safety Manual should be observed. for damages and / or losses related to such security breaches,...
  • Page 7 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Note IECEx intrinsic safety • Further information on the approval of devices for use in Approved for use in Zone 0, 1, and 2.
  • Page 8 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Temperature data Electrical data Transmitter Transmitter ATEX / IECEx intrinsic safety, ATEX non-sparking and increased Intrinsic safety type of protection Ex ia IIC (part 1)
  • Page 9 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Installation instructions Intrinsic safety type of protection Ex ia IIC (part 2) ATEX / IECEx The installation, commissioning, maintenance and repair of TTH300-E1P, TTH300-H1P, TTH300-E1F, TTH300-H1F devices in potentially explosive atmospheres must only be carried out by appropriately trained personnel.
  • Page 10 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Installation instructions Electrical connections Installation in a potentially explosive atmosphere Grounding Transmitters can be installed in all kinds of industrial sectors.
  • Page 11 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G ATEX – Zone 1 (0) ATEX – Zone 1 (20) Marking: II 2 (1) G Ex [ia IIC Ga] ib IIC T6...T1 Gb Marking: II 2 G (1D) Ex [ia IIIC Da] ib IIC T6...T1 Gb...
  • Page 12 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Installation instructions Commissioning ATEX – Zone 2 The commissioning and parameterization of the device may also Marking: be carried out in potentially explosive atmospheres using a II 3 G Ex nA IIC T6...T1 Gc...
  • Page 13 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 3 Use in potentially explosive atmospheres in accordance with FM and CSA Note CSA Non-Incendive • Further information on the approval of devices for use in potentially explosive atmospheres can be found in the...
  • Page 14 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 3 Use in potentially explosive atmospheres in accordance with FM and CSA Installation instructions FM / CSA Field (Ex area) Control room (safe area) The installation, commissioning, maintenance and repair of devices in areas with explosion hazard must only be carried out by appropriately trained personnel.
  • Page 15 They conform to the Sensor Redundancy requirements of IP rating IP 20 and are suited for integration To enhance system availability, the TTH300 has two sensor into DIN A and DIN B sensor heads. inputs. The second sensor input can be used redundantly for both With HART®...
  • Page 16 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 4 Design and function … Input functionality Redundancy behavior Output behavior (behavior of the Current output assignment to Redundancy configuration to be Diagnostic message to be set current output) be set (Tools: “HART Mapping”) set (Tools: “Parameter setting”)
  • Page 17 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Sensor drift monitoring Sensor drift monitoring with redundancy operation (devices If two sensors are connected, sensor drift monitoring can be with HART® from SW-Rev. 3.00) FDI Package (FIM) enabled via DTM, EDD or...
  • Page 18 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 5 Product identification Name plate Note Products that are marked with the adjacent symbol may not be disposed of as unsorted municipal waste (domestic waste). They should be disposed of through separate collection of electric and electronic devices.
  • Page 19 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 6 Transport and storage 7 Installation Inspection DANGER Check the devices immediately after unpacking for possible Improper installation and commissioning of the device damage that may have occurred from improper transport. carries a risk of explosion.
  • Page 20 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 7 Installation Installation options Installation in the cover of the connection head There are three options for installing the transmitter: • Installation in the cover of the connection head (without springs) •...
  • Page 21 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 8 Electrical connections Installing / removing the optional LCD Safety instructions indicator DANGER The transmitter can be optionally equipped with an LCD Improper installation and commissioning of the device indicator. carries a risk of explosion.
  • Page 22 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 8 Electrical connections Protection of the transmitter from damage caused by highly energetic electric interferences The transmitter has no switch-off elements. Therefore, Suited protective measures overcurrent protective devices, lightning protection, or voltage The following items should be observed to protect the disconnection options must be provided at the plant.
  • Page 23 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Terminal assignment Resistance thermometers (RTD) / resistors (potentiometer) A Potentiometer, four-wire circuit H RTD, two-wire circuit B Potentiometer, three-wire circuit I Sensor 1 C Potentiometer, two-wire circuit J Sensor 2* D 2 × RTD, three-wire circuit* K Interface for LCD indicators and service E 2 ×...
  • Page 24 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 8 Electrical connections … Terminal assignment Thermocouples / voltages and resistance thermometer (RTD) / thermocouple combinations A 2 × voltage measurement* G 1 × RTD, two-wire circuit and 1 x thermocouple* B 1 ×...
  • Page 25: Input - Thermocouples / Voltages

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Electrical data for inputs and outputs Input - resistance thermometer / resistances Input - thermocouples / voltages Resistance thermometer Types • Pt100 in accordance with IEC 60751, JIS C1604, MIL-T-24388 • B, E, J, K, N, R, S, T in accordance with IEC 60584 •...
  • Page 26: Output - Hart

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 8 Electrical connections … Electrical data for inputs and outputs Output – HART® Output – PROFIBUS PA® Note Note The HART® protocol is an unsecured protocol, as such the The PROFIBUS PA® protocol is an unsecured protocol, as such...
  • Page 27: Output - Foundation Fieldbus

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Output – FOUNDATION Fieldbus® Power supply Two-wire technology, polarity safe; power supply lines = signal lines Note The FOUNDATION Fieldbus® protocol is an unsecured protocol, as such the intended application should be assessed to ensure Note that these protocols are suitable before implementation.
  • Page 28: Power Supply - Profibus / Foundation Fieldbus

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 8 Electrical connections … Electrical data for inputs and outputs Voltage drop on the signal line Power supply – PROFIBUS / FOUNDATION Fieldbus When connecting the devices, note the voltage drop on the signal line.
  • Page 29: Commissioning

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 9 Commissioning General In case of corresponding order the transmitter is ready for The device is listed with the FieldComm Group. operation after mounting and installation of the connections. The parameters are set at the factory.
  • Page 30: Configuration Options / Tools

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 9 Commissioning … Communication Configuration options / tools PROFIBUS® Communication Driver-independent: Note • HMI LCD indicator with configuration function The PROFIBUS PA® protocol is an unsecured protocol, as such Driver-dependent: the intended application should be assessed to ensure that •...
  • Page 31: Foundation Fieldbus® Communication

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Basic Setup Note FOUNDATION Fieldbus® Communication The communication and configuration of the transmitter via Note HART, PROFIBUS PA and FOUNDATION Fieldbus H1 are described The FOUNDATION Fieldbus® protocol is an unsecured protocol, in the separate documentation “Interface Description”...
  • Page 32: 10 Operation

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 10 Operation Safety instructions For transmitters that support HART 7, switch 2 allows the If there is a chance that safe operation is no longer possible, desired HART version to be set (HART 5 or HART 7).
  • Page 33: Menu Navigation

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu navigation Menu Exit Select 1 Operating buttons for menu 4 Marking to indicate relative navigation position within the menu 2 Indication of menu designation 5 Indication of the current function assigned to the operating...
  • Page 34: Hart® Menu Levels

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Menu navigation HART® menu levels To SW-Rev. 1.03 Process display Configuration level Device Setup Device Info Display Process Alarm Communication Calibrate Diagnosis From SW-Rev. 3.00 Process display Information level with...
  • Page 35: Profibus Pa® And Foundation Fieldbus® H1 Menu Levels

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G PROFIBUS PA® and FOUNDATION Fieldbus® H1 menu levels Process display Information level Configuration level Diagnosis Device Setup Operator Page 1 Device Info Operator Page 2 Communication Autoscroll Service Signal View Display Calibrate Process display The process display shows the current process values.
  • Page 36: Process Display

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation Process display Error messages in the HART® LCD display In the event of an error, different information appears depending on the revision: • To SW-Rev. 1.03: A symbol or letter (Device Status) and a number (DIAG.NO.)
  • Page 37: Error Messages In The Lcd Display Profibus Pa® And Foundation Fieldbus

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Error messages in the LCD display PROFIBUS PA® and The error can then be read in plain text via the information level FOUNDATION Fieldbus® “Diagnosis” (from SW-Rev. 3.00). In the event of an error, a message consisting of a symbol and...
  • Page 38: Switching To The Information Level

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation Switching to the configuration level Switching to the information level (parameterization) (only for PROFIBUS PA, FOUNDATION Fieldbus and HART from SW-Rev. 3.00) The device parameters can be displayed and changed on the On the information level, the operator menu can be used to configuration level.
  • Page 39: Selecting And Changing Parameters

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Selecting and changing parameters Entry from table Parameter name When an entry is made from a table, a value is selected from a 12.3456 [unit] list of parameter values. Menu name Next...
  • Page 40: Parameter Overview Hart® (For Devices To Sw-Rev. 1.03)

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation Parameter overview HART® (for devices to SW-Rev. 1.03) Note This overview of parameters shows all the menus and parameters available on the device. Depending on the version and configuration of the device, not all of the menus and parameters may be visible in it.
  • Page 41 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Calibrate Measured range Apply Lower Range Apply Upper Range Analog Out Trim 4 mA Trim 20 mA Diagnosis Looptest Device status Temp. of Electronics Sensor 1 process data Sensor 2 process data...
  • Page 42: Parameter Description Hart® (For Hart®-Devices To Sw-Rev. 1.03)

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation Parameter description HART® (for HART®-devices to SW-Rev. 1.03) Menu: Device Setup Menu / parameter Description … / Device Setup Write protection Activates write protection for the entire device •...
  • Page 43 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu / parameter Description … / Device Setup / Input Sensor 1 … / Device Setup / Input Sensor 2 Sensor Type Selection of the sensor type (continued): • –125 ... 125 mV: Linear voltage measurement -125 to 125 mV •...
  • Page 44 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description HART® (for HART®-devices to SW-Rev. 1.03) Menu / parameter Description R-Connection Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers • two-wire: Sensor connection type in two-wire technology •...
  • Page 45: Menu: Device Info

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu: Device Info Menu / parameter Description … / Device Info Device Type Displays device type. Serial Number Displays device serial number. Software Version Displays device software version. Hardware Version Displays device hardware version.
  • Page 46: Menu: Process Alarm

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description HART® (for HART®-devices to SW-Rev. 1.03) Menu: Process Alarm Menu / parameter Description … / Process Alarm Fault signaling • Underrange: in the event of an error, the current, for example 3.6 mA, is output •...
  • Page 47: Menu: Diagnosis

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu: Diagnosis Menu / parameter Description … / Diagnosis Looptest Simulates the current output signal Value range: 0 to 23.600 mA Device status Diagnosis notice (maintenance required, error, etc.) Temp. of Electronics...
  • Page 48: Parameter Overview Hart® (For Hart-Devices From Sw-Rev. 3.00)

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation Parameter overview HART® (for HART-devices from SW-Rev. 3.00) Note This overview of parameters shows all the menus and parameters available on the device. Depending on the version and configuration of the device, not all of the menus and parameters may be visible in it.
  • Page 49 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Device Setup Write protection Input Sensor 1 Sensor Type R-Connection 2-wire Resistance Input Sensor 2 Thermocouple CJC Ext. CJC Temperature Input / output assignment Redundancy Configuration PV Measured range PV Unit PV Damping...
  • Page 50 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter overview HART® (for HART-devices from SW-Rev. 3.00) Calibrate Measured range Apply Lower Range Apply Upper Range Analog Out Trim 4 mA Trim 20 mA Diagnosis Looptest Device status...
  • Page 51: Parameter Description Hart® (For Hart®-Devices From Sw-Rev. 3.00)

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Parameter description HART® (for HART®-devices from SW-Rev. 3.00) Menu: Easy Setup Menu / parameter Description … / Easy Setup Language Selection of the menu language. • German • English HART TAG Measuring point tagging •...
  • Page 52 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description HART® (for HART®-devices from SW-Rev. 3.00) Menu / parameter Description … / Easy Setup Selection of the sensor type (continued): • −125 to 125 mV: Linear voltage measurement −125 to 125 mV •...
  • Page 53 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu / parameter Description … / Easy Setup R-Connection S2 Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers • Two-wire: sensor connection type in two-wire technology • Three-wire: sensor connection type in three-wire technology •...
  • Page 54: Menu: Device Setup

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description HART® (for HART®-devices from SW-Rev. 3.00) Menu: Device Setup Menu / parameter Description … / Device Setup Write protection Activates write protection for the entire device •...
  • Page 55: Menu: Display

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu: Display Menu / parameter Description … / Display Language Language selects the menu language. • German • English Contrast Sets the display contrast Value range: 0 to 100 % Mode Operator Page 1...
  • Page 56: Menu: Communication

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description HART® (for HART®-devices from SW-Rev. 3.00) Menu: Communication Menu / parameter Description … / Communication HART TAG Measuring point tagging • 8 characters LONG TAG Long tag: Unique label of the device in the plant (from HART 7) •...
  • Page 57: Menu: Calibrate

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu: Calibrate Menu / parameter Description … / Calibrate Select the ‘Measured range’ submenu. Measured range Select the ‘Analog Out’ submenu. Analog Out … / Calibrate / Measured range Apply Lower Range The current reading (PV) is used as the lower range limit (4 mA).
  • Page 58: Menu: Device Info

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description HART® (for HART®-devices from SW-Rev. 3.00) Menu: Device Info Menu / parameter Description … / Device Info Device Type Displays device type. Serial Number Device 7 or 8-digit serial number of the device electronic unit.
  • Page 59: Profibus Pa® Und Foundation Fieldbus® Parameter Overview

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G PROFIBUS PA® und FOUNDATION Fieldbus® Parameter overview Note This overview of parameters shows all the menus and parameters available on the device. Depending on the version and configuration of the device, not all of the menus and parameters may be visible in it.
  • Page 60: Parameter Description Profibus Pa® And Foundation Fieldbus

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation Parameter description PROFIBUS PA® and FOUNDATION Fieldbus® Menu: Device Setup Menu / parameter Description … / Device Setup Sensor 1 / Sensor 2 Selects sensor type: • Pt100 (IEC751): Resistance thermometer Pt100 (IEC751) •...
  • Page 61 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu / parameter Description (continuation) Sensor 1 / Sensor 2 Selection of the sensor type (continued): • Ni50 (DIN43760): Resistance thermometer Ni50 (DIN43716) • Ni100 (DIN43760): Resistance thermometer Ni100 (DIN43716) • Ni120 (DIN43760): Resistance thermometer Ni120 (DIN43716) •...
  • Page 62: Menu: Device Info

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description PROFIBUS PA® and FOUNDATION Fieldbus® Menu: Device Info Menu / parameter Description … / Device Info Device ID Displays device ID Serial Number Displays serial number...
  • Page 63: Menu: Service Menu

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Menu: Service Menu Menu / parameter Description … / Service Menu Device temperature Select the ‘Device temperature’ submenu. Sensor 1 Select the ‘Sensor 1’ submenu. Sensor 2 Select the ‘Sensor 2’ submenu.
  • Page 64: Menu: Display

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 10 Operation … Parameter description PROFIBUS PA® and FOUNDATION Fieldbus® Menu: Display Menu / parameter Description … / Display Language Selects the menu language • German • English Contrast Sets the display contrast...
  • Page 65: Factory Settings

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Factory settings Firmware settings The transmitter is configured ex works. HART® devices from SW-Rev. 3.00 These devices can be reset to the factory setting, as well as to the setting according to the customer order.
  • Page 66: 11 Diagnosis / Error Messages

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 11 Diagnosis / error messages Diagnostic information Monitoring of operating data The transmitter saves the highest and lowest values for the electronic unit temperature as well as measured values from sensor 1 and sensor 2 in the non-volatile memory (‘Drag Indicator’).
  • Page 67: Calling Up The Error Description

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Calling up the error description For devices with PROFIBUS PA, FOUNDATION Fieldbus and HART® from SW-Rev. 3.00 Additional details about the error that has occurred can be called up on the information level.
  • Page 68: Possible Error Messages - Hart® Devices To Sw-Rev. 1.03

    TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G … 11 Diagnosis / error messages Possible error messages – HART® devices to SW-Rev. 1.03 Range Displays the Displays the Cause Remedy device DIAG. NO. status Electronics Device defective Replace the device...
  • Page 69 Lower limit value: alarm Operating conditions Limit HIGH Upper limit value: warning Operating conditions Limit LOW Lower limit value: warning Note If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
  • Page 70: Possible Error Messages - Hart® Devices From Sw-Rev. 3.00

    Verify process or change limit value Configuration Parameterization / config. failure Error Load valid param restart (RESET), reset to factory Note If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
  • Page 71: Possible Error Messages - Profibus Pa® And Foundation Fieldbus

    Rectify short-circuit at sensor 2 or replace sensor 2 Sensor Sensor 2 redundancy, wire break Maintenance required Rectify break at sensor 2 or replace sensor 2 Note If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
  • Page 72 12. disposal or must observe the following regulations for shipping purposes: All devices delivered to ABB must be free from any hazardous materials (acids, alkalis, solvents, etc.). Please contact Customer Center Service acc. to page 6 for...
  • Page 73 14 Recycling and disposal 15 Specification Note Note The device data sheet is available in the ABB download area at Products that are marked with the adjacent symbol may not be disposed of as unsorted municipal waste www.abb.com/temperature. (domestic waste).
  • Page 74 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G 17 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
  • Page 75 TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G Notes...
  • Page 76 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

Table of Contents