3.9.2
Configuring SITOP software for PCU Base Software
The SITOP monitor has to be started by Windows automatically during ramp-up: Activate
this setting when installing the SITOP software in the dialog "Configuration - default settings
for the SITOP Software". Select the option "Start program with Windows". After the PCU has
restarted, the SITOP monitor is then automatically started. The next installation step is to
configure the SITOP monitor.
Precondition
● The SITOP UPS hardware is connected via the USB interface
● The SITOP software of version 3.x.2.16 or later is installed in directory
● The SITOP software is installed as a normal application, not as a Windows service.
Note
Windows service of the SITOP software not compatible with PCU Base Software
If you use SITOP as a Windows service with the PCU Base Software, the correct switch-off
procedure cannot be performed!
PCU Base Software (IM10)
Commissioning Manual, 03/2013, 6FC5397-1DP40-3BA1
3.9 Configuring the SITOP UPS module for use with the PCU Base Software
Configuration of the system
E:\SITOP\
31