Basic software procedures
Ê Select your preferred user interface language.
Ê Under Status backup media select No status backup and click Continue.
Ê Select Maintenance.
Ê Select Server Configuration Manager.
Ê Check the box for rack model and save the setting by clicking Save.
Using the ServerView Maintenance Tools
On Windows-based servers with ServerView agents installed, proceed as
follows:
Ê Click Start, point to All Programs, and then point to Fujitsu - ServerView
Suite - Agents - Maintenance Tools.
Ê In the Maintenance Tools menu pane, click the Chassis Model
Configuration tab.
Ê Under Convert to click the Rack Model button.
Ê Click Exit to close the Maintenance Tools menu pane.
I
For more information on installing ServerView agents, see the
"ServerView Operations Manager - Installation ServerView Agents for
Windows" user guide.

5.2.21 Performing a fan test

I
Notes on replacing a defective fan
After replacing a defective system fan or PSU containing a defective fan,
the fan error indicators will stay lit until the next fan test. By default, a fan
test is automatically started every 24 hours. The first automatic fan test
being performed after replacing a fan will turn off the fan error indicator.
If you want to start the fan test manually, you can do so by following the
description below:
Executing the fan test via the iRMC web interface
Ê Log into the iRMC web interface.
The System menu is displayed on default.
Ê Open the Cooling page.
124
Upgrade and Maintenance Manual
TX1330 M4