Performing a fan test

Notes on replacing a defective fan
After replacing a defective system fan or PSU containing a defective fan,
the fan error indicators will stay lit until the next fan test. By default, a fan
test is automatically started every 24 hours. The first automatic fan test
being performed after replacing a fan will turn off the fan error indicator.
If you want to start the fan test manually, you can do so by following the
description below:
Executing the fan test via the iRMC S6 web interface
▶ Log into the iRMC S6 web interface.
The System menu is displayed on default.
▶ Open the Cooling page.
▶ Expand the Cooling Devices group.
▶ Click Start Fan Test.
For more information on iRMC settings, see the iRMC user guides.