Table 2 2. Module Backplane Slot Connections - Ametek Elgar ReFlex Power Operation Manual

Table of Contents

Advertisement

Mainframe
Table 2-2. Module Backplane Slot Connections
Module Model
RFP-C1LAN-000-xxxx
RFP-F1000-001-xxxx
RFP-D1016-021-xxxx
RFP-D1065-5A1-xxxx
RFP-D2033-030-xxxx
RFP-D2050-020-xxxx
RFP-D2050-025-xxxx
RFP-D2120-8A3-xxxx
RFP-D2450-2A3-xxxx
RFP-A30XK-875-xxxx
RFP-L3500-750-xxxx
RFP-L3500-375-xxxx
The maximum output power per single group of four slots is produced when two
HPDC 1kW modules are installed in the group. This sets the maximum
aggregate output power limit of the Mainframe at 6kW. The resultant maximum
current per input connector line and per input service line is presented in Table
2-3. In general, to determine the actual input currents, the current requirements
of the modules that are installed in each group must be summed. This would
determine the requirement for the AC/DC input overcurrent protection current
rating.
2-16
Number
Slot Supplying
Width
of Slots
Occupied
single
1
single
single
1
single
single
1
single
double
2
right-most
triple
3
right-most
triple
3
right-most
Maximum Input
Current
Input Power
(at 103.5VAC and
full load)
0.2A
2.8A
4A
12A
12A
1.1A
ReFlex Power™