AC Power Supplies
Twisting the load wires provides an additional benefit in reducing the parasitic
inductance of the cable. This improves the dynamic response characteristics at
the load by maintaining a low source impedance at high frequencies. Also, with
long load wires, the resultant inductance and resistance could produce high
frequency voltage fluctuations at the load because of current variations in the
load itself.
4.5

OPERATION

The AC power supply module function within the ReFlex Power™ system under
remote control through a host controller. The ReFlex Power™ Controller module
serves as a communications portal between the power supply modules and the
remote host controller. All aspects of operation could be achieved through use of
commands that comply with the requirements of the SCPI Standard 1997
command language. Additional discrete digital and optional analog control
signals are available for dedicated hardware interface. All connectors for control
and power interface are accessible on the front panel
4-28