Ametek Elgar ReFlex Power Operation Manual page 162

Table of Contents

Advertisement

ReFlex Power™
14. Set the output frequency to 500Hz
15. Wait for AC current to stabilize. Measure the output current using the AC meter.
Enter the measured current using following command
16. Set the output frequency to 1000Hz
17. Wait for AC current to stabilize. Measure the output current using the AC meter.
Enter the measured current using following command
18. Set the output frequency to 2000Hz
19. Wait for AC current to stabilize. Measure the output current using the AC meter.
Enter the measured current using following command
20. Set the output frequency to 3000Hz
21. Wait for AC current to stabilize. Measure the output current using the AC meter.
Enter the measured current using following command
22. Set the output frequency to 4000Hz
23. Wait for AC current to stabilize. Measure the output current using the AC meter.
Enter the measured current using following command
24. Set the output frequency to 5000Hz
25. Wait for AC current to stabilize. Measure the output current using the AC meter.
Enter the measured current using following command
M380056-01 Rev L
SOUR<n>:FREQ 500
CAL<n>:OUTP:FREQ:CURR2 <value-2>
SOUR<n>:FREQ 1000
CAL<n>:OUTP:FREQ:CURR3 <value-3>
SOUR<n>:FREQ 2000
CAL<n>:OUTP:FREQ:CURR4 <value-4>
SOUR<n>:FREQ 3000
CAL<n>:OUTP:FREQ:CURR5 <value-5>
SOUR<n>:FREQ 4000
CAL<n>:OUTP:FREQ:CURR6 <value-6>
SOUR<n>:FREQ 5000
CAL<n>:OUTP:FREQ:CURR7 <value-7>
AC Power Supplies
4-77