12. Program the output voltage to 50% of the full scale voltage
13. Wait for AC voltage to stabilize. Measure the output voltage using the AC
voltmeter. Enter the measured voltage using following command
14. Program the output voltage to 72.5% of the full scale voltage
15. Wait for AC voltage to stabilize. Measure the output voltage using the AC
voltmeter. Enter the measured voltage using following command
16. Program the output voltage to 95% of the full scale voltage
17. Wait for AC voltage to stabilize. Measure the output voltage using the AC
voltmeter. Enter the measured voltage using following command
18. Perform the voltage calibration using following command
19. Send the system error query command to make sure calibration was successful.
20. If there is no error returned at the system error query command then save the
calibration result with the following command
21. Optional Commands:
Query the voltage calibration points: CAL<n>:OUTP:VOLT:FIVEPOINT ?
22. Reset the unit
4-64
CAL<n>:OUTP:VOLT:FIVEPOINT2 <value-2>
CAL<n>:OUTP:VOLT:COUNTS 9649
CAL<n>:OUTP:VOLT:FIVEPOINT3 <value-3>
CAL<n>:OUTP:VOLT:COUNTS 13990
CAL<n>:OUTP:VOLT:FIVEPOINT4 <value-4>
CAL<n>:OUTP:VOLT:COUNTS 18332
CAL<n>:OUTP:VOLT:FIVEPOINT5 <value-5>
CAL<n>:OUTP:VOLT:CALC
SYST:ERR?
CAL<n>:UNLOCK "6867"
CAL<n>:STORE
CAL<n>:LOCK
*RST<n>