7-3-7

Terminal AM (Analog Output)

The terminal AM provides an analog output of 0 to 10 VDC.
The digital terminal AM on the control circuit terminal block enables the monitoring of the output fre-
quency and the output current.
The analog output may not stabilize immediately after the power is turned on or off.
AM Selection
Select the signal you want to output from the following table.
Parameter
Function
No.
AM
C028
Selection
*1. 07 (LAD frequency) represents the frequency commanded by the inverter and is equivalent of the Output Fre-
quency Monitor (d001) value. 00 (Output frequency) represents a frequency value that takes into account the
aspects of vector control compensation (such as sensorless vector control) and even stabilization control.
When set to 00 (Output frequency), the parameter may produce an output that appears to be unstable at low
speeds, for example, when decelerating due to the overload limit function. In this case, set it to 07 (LAD fre-
quency) to obtain a stable output.
*2. Setting the Pulse Train Input EA Selection (P003) to 01 (Feedback pulse) causes the inverter to output the
frequency displayed in the Real Frequency Monitor (d008).
*3. This setting is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless vector con-
trol). When A044/A244 is not set to 03, the inverter does not produce output because it remains at 0 V.
*4. The specifications of the output torque (signed) are as follows.
AM output [V]
10
5
0
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Data
name
00
Output frequency
01
Output current
02
Output torque
04
Output voltage
05
Input power
06
Electronic thermal load rate
07
LAD frequency
10
Cooling fin temperature
11
Output torque (signed)
13
DriveProgramming (YA(1))
16
Option (No applicable Option)
AM Gain Setting (C106) = 200%
100
200
Description
*1 *2
0 to Maximum frequency [Hz]
0 to 200%
*3
0 to 200%
0 to 133%
(Example: For 200-V class, 7.5 V at
200 V)
0 to 200%
0 to 100%
*1
0 to Maximum frequency [Hz]
0 to 200°C (Outputs 0°C for 0°C or
lower)
*3
0 to 200%
Use DriveProgramming to set this
function.
(0.00 to 100.00%)
AM Gain Setting (C106) = 100%
AM Bias Setting (C109) = 50%
Torque [%]
7 Other Functions
Full-scale value
*4
7 - 29
7