Output Terminal Functions

The output terminal function, which sets the output methods by switching the settings of H2-01 to H2-03
(Multi-function contact output terminals M1-M2, P1-PC, and P2-PC), is described here.
During Run (Setting: 0)
OFF
ON
During Run 2 (Setting: 37)
OFF
ON
These outputs can be used to indicate the Inverter's operating status.
Zero-speed (Setting: 1)
OFF
ON
Output frequency
Zero-speed output
-92
6
The Run Command is OFF and there is not output voltage.
The Run Command is ON or a voltage is being output.
The Inverter is not outputting a frequency. (Baseblock, DC injection braking, initial excitation, or
stopped)
The Inverter is outputting a frequency.
OFF
ON
Run Command
OFF
Baseblock command
Output frequency
OFF
ON
During run 1 output
OFF
During run 2 output
Fig 6.54 Timing Chart for "During RUN" Output
The output frequency is greater than the minimum output frequency (E1-09).
[With flux vector control, is greater than the zero-speed level (b2-01).]
The output frequency is less than the minimum output frequency (E1-09).
[With flux vector control, is less than the zero-speed level (b2-01).]
OFF
Fig 6.55 Timing Chart for Zero-speed
ON
ON
Minimum output frequency (E1-09)
[Zero-speed level (b2-01) when flux vector control is
being used.]
ON