First Operation Of The Spindle - Omron SPINOGY 3G3MX2 Quick Start Manual

Table of Contents

Advertisement

Parameters for DC-Brake
Compared to the normal deceleration to stop, the DC braking function provides additional stopping torque. This
setting is recommended by SPINOGY because in case of an emergency stop, the spindle is decelerated faster.
Func. code
Name
A051
DC injection braking selection
Parameters for PTC-Thermistor
SPINOGY spindles are equipped with a PTC in the base configuration. To parameterize this in the frequency
inverter, the following values are necessary.
Func. code
Name
Multi-function input [5] [PTC
C005
assignable]
C085
Thermistor adjustment
04.6

First operation of the spindle

When the basic parameters have been programmed and the spindle has been properly connected, the entire
system is ready for use. To start a first test run via the keypad, parameter A001 must be set to the value 02 and
parameter A002 must also be set to the value 02. The following steps must be carried out for the first spindle
start:
01. Verify the power LED is ON. If not, check the power connections.
02. Verify the Run Key Enable LED is ON. If it is OFF, check the A002 setting.
03. Make sure the spindle is disconnected from any mechanical load.
04. Parameter F001 must be called up and checked whether it shows 0.00. If not, press the key
decrease the value.
05. Now the RUN key on the keypad can be pressed. The "RUN" LED lights up.
06. The key
.
07. Press the STOP key to stop the motor rotation.
04 Commissioning
must be pressed for a few seconds. The motor should start.
Description
Three options, select codes:
00... OFF (Disabled)
01... ON (Enabled)
02... ON (Freq.) (Frequency control [A052])
Description
19: PTC-Thermistor
Scale factor of PTC input. Range is 0.0 to 200.0%
to
18