Download Print this page

Keypad Operation - Omron JZA24P0BAA Quick Start Manual

Compact general purpose inverter, 200/400 v class three-phase input 0.1/0.2 to 0.4/1.5/4.0 kw

Advertisement

4 Keypad Operation

4
Keypad Operation
LED Operator and Keys
The LED operator is used to program the drive, to start/
stop it, and to display fault information. The LEDs indi-
cate the drive status.
Keys and Functions
Display
Name
Data Display Area Displays the frequency reference, parameter number, etc.
ESC Key
RESET Key
RUN Key
RUN
Up Arrow Key
Down Arrow Key
STOP Key
STOP
ENTER Key
LO/RE
Key
ALM LED Light
ALM
REV LED Light
REV
DRV LED Light
DRV
FOUT LED Light
FOUT
16
Returns to the previous menu.
Moves the cursor to the right.
Resets a fault.
Starts the drive in the LOCAL mode. The Run LED
• is on, when the drive is operating the motor.
• flashes during deceleration to stop or when the frequency reference is 0.
• flashes quickly the drive is disabled by a DI, the drive was stopped using a fast
stop DI or a run command was active during power up.
Scrolls up to select parameter numbers, setting values, etc.
Scrolls down to select parameter numbers, setting values, etc.
Stops the drive.
Selects modes, parameters and is used to store settings.
Switches drive control between the operator (LOCAL) and the control circuit
Selection
terminals (REMOTE). The LED is on when the drive is in the LOCAL mode
(operation from keypad).
Flashing: The drive is in an alarm state.
On: The drive is in a fault state and the output is stopped.
On: The motor rotation direction is reverse.
Off: The motor rotation direction is forward.
On: The drive is ready to operate the motor.
Off: The drive is in the Verify, Setup, Parameter Setting mode.
On: The output frequency is displayed on the data screen.
Off: Anything else than the output frequency is displayed on the data screen.
Function
I80E-EN
J1000 Quick Start Guide
STOP

Advertisement

loading

This manual is also suitable for:

JzaJ1000Jzab0p1baa