11.1 Introduction of AHRTU-DNET-5A

1. Thank you for choosing Delta AHRTU-DNET-5A. To ensure correct installation and operation of
the device, please read the instruction carefully before use.
2. This manual only provides introductory information on AH10PFBS-5A. Detailed information
about DeviceNet protocol is not included in this manual. Please refer to relevant literatures for
more information on DeviceNet protocol.
3. Defined as a remote I/O module for data exchange, AHRTU-DNET-5A is used for connecting
AH500 series I/O module, analog I/O module, temperature module and AH10SCM-5A module
to the DeviceNet network.

11.1.1 Feature

It supports the standard DeviceNet communication protocol as the DeviceNet slave.
It supports explicit connection via predefined Master/Slave connection set.
It supports polling.
The network configuration software DeviceNet Builder provides the graphic configuration
interface, automatically scans and identifies I/O modules, randomly maps the parameters of
special modules as I/O exchange data, sets the methods to deal with the errors and diagnoses
the error status of each module.
According to the actual need, users select whether to retain the buffer register information when
the network is offline.
It is can be connected to one main rack, 7 extension racks and 68 AH500 series I/O modules.
The maximum input and output data it supports: 980 bytes respectively
It supports a hot swap. (When power ON, the device can be plugged directly for use after being
removed.)

11.1.2 Function and Specifications

DeviceNet connection
Item
Transmission method
Electric isolation
Interface
Transmission cable
Voltage
Current
DeviceNet communication
Item
Communication protocol
Message type
Baud rate
Ch a pt er 11 DeviceNet Re m ote I/O Module AHRTU-DNET
Specification
CAN
DC 500 V
Removable connector (5.08 mm)
2 communication wires, 2 power wires and 1 shielded wire
(The shielded wire must be connected to the ground and the
communication wire must keep away from the power cable)
11~25 V DC, supplied by DeviceNet network
60 mA
Specification
Standard DeviceNet communication protocol
I/O polling, explicit, Group 2 only servers
Standard: 125 kbps; 250 kbps; 500 kbps
Extension: 10 kbps; 20 kbps; 50 kbps; 125 kbps; 250 kbps;
500 kbps; 800 kbps; 1Mbps