Ch a pt er 6 Tem per at u r e M eas ur em ent M o d u le A H 04T C / AH 08T C
b. Interrupt service routine
The procedure below explains how to trigger an interrupt service routine in a CPU module.
The interrupt service routines are I40~I251.
7. PID control
a. KP/KI/KD
Proportional action: The operation amount acts proportionally to the error. When a
Heater: The setting value is 1000 (100°C), and K
temperature and the operation amount is shown below.
O pe ra tio n a mou nt
He ate r
No (No detection)
No
No interrupt
temperature is lower than a proportional band, the operation amount is
100%. When a temperature is within a proportional band, the operation
amount decreases proportionally to the error. When the setting value is
the same as the present value, the operation amount is 0%.
(Error=Setting value–Present value)
1 00 %
0 %
Proportional
9
0℃
band
Channel
detection
Alarm/Warning
Enabling
physical range
detection
Yes
Enabling
interrupts
Yes
Selecting interrupt
numbers
is 100 (10°C). The relation between the
P
Te mpe ra tur e
1
00℃
6 - 9