13.1 Introduction of AH10PFBS-5A

1. Thank you for choosing Delta AH10PFBS-5A PROFIBUS-DP slave module. To ensure correct
installation and operation of the product, please read this operation manual carefully before
use.
2. This operation manual only provides introductory information on AH10PFBS-5A. Detailed
information about PROFIBUS-DP protocol is not included in this manual. Please refer to
relevant literatures for more information on PROFIBUS-DP protocol.
3. AH10PFBS-5A is a PROFIBUS-DP slave module for connecting Delta's AH500 series CPU
module to PROFIBUS-DP network. It does not need to be externally connected with the power
supply since its power is supplied by the rack.
4. The power module AHPS05-5A, an AH500 series PLC and the main rack are necessary for
using AH10PFBS-5A.
5. AH10PFBS-5A can only be connected to the I/O slot of the main AH500 series rack instead of
the extension rack.
13.1.1 Functions
Supports PROFIBUS-DP cyclic data transmission between the master and multiple slaves
Auto-detects baud rates; supports max. 12 Mbps
Self-diagnosis
Supports hot-plugging (The module could be inserted to or removed from the main rack when
the main rack is powered ON.)
The main rack can connect 8 AH10PFBS-5A modules at most.
The I/O data of each AH10PFBS-5A supports max. 100 words of data input and 100 words of
data output.

13.2 Product Profile and Outline

13.2.1 Parts
1. Model Name
4. PROFIBUS-DP COM port
7. Set screw
1 3 - 2
2. Digital Displayer
5. RUN indicator
8. Nameplate
3. Address switch
6. NET indicator
9. Module fixing projection